PZH HDT*/A is a range of surge protection devices designed for the protection of data, communication, measuring and control lines against surge effects. These devices are recommended for use at the boundaries of LPZ 1-2-3 lightning protection zones according to EN 62305. All types provide effective protection of connected equipment against common mode and differential mode surge effects according to EN 61643-21. The rated load current of individual protected lines IL = 5 A. 1st stage is solved by using three-pole gas discharge tubes. The number of protected pairs is optional (1-2). PZH HDT*/A is produced for nominal operating voltage of 48 V.
| Montageart | Hutschiene TH35 |
| Nennableitstoßstrom (8/20) | 15 kA |
| Blitzstoßstrom (10/350 µs) | 2,5 kA |
| Nennlaststrom | 5 A |
| Höchste Dauerspannung DC | 57,6 V |
| Schutzpegel Ader/Ader | 270 V |
| Schutzpegel Ader/Erde | 450 V |
| Grenzfrequenz | 100 MHz |
| Anschluss 1 | Klemme |
| Mit Fernmeldekontakt | Falsch |