PZH R1 25G* is a lightning and surge arrester according to EN 61643-11 ed.2 (IEC 61643-11:2011). It consists of high energy double varistors for better discharge ability and a gas discharge tube connected in series, which ensures zero leakage current through the conductor. Its parameters enable usage in buildings with considerable levels of protection LPL I and LPL II, such as hospitals, banks, industrial and administration complexes, schools, shopping and sports centres or supermarkets. The device is to be installed on the interface of LPZ 0 – LPZ 1 and higher zones according to standard EN 62305 ed.2 (IEC 62305:2010), closest to where overhead line enters the building i.e. in the main distribution boards. The product has two PEN terminals, which can not be used as a PEN bridge. S indication specifies a version with remote monitoring.
| Netzform TN-C-S | Falsch |
| Netzform DC | Falsch |
| Nennspannung AC | 230 V |
| Blitzstoßstrom (10/350 µs) | 25 kA |
| Netzform IT | Falsch |
| Höchste Dauerspannung AC | 255 V |
| Netzform TN-C | Wahr |
| Netzform TN-S | Falsch |
| Netzform TT | Falsch |
| Polzahl | 3 |
| Schutzpegel | 1,2 kV |
There are currenty no files for your language.